Table 3-3 NetCol8000-C070 cable specifications
Applica
tion
Scenari
o
Indoor
unit
Teamwo
rk and
monitori
ng
network
cables
Issue 09 (2022-12-15)
Name
Power cable
(without
heating and
humidification)
Power cable
(with heating
and
humidification)
Equipotential
ground cable
Standard
network cable
Copyright © Huawei Digital Power Technologies Co., Ltd.
Technical Requirements
2
4 x 2.5 mm
2
4 x 4 mm
2
6 mm
outdoor copper cable
Signal cable, shielded
straight-through cable, 10 m,
MP8-II, CC4P0.5GY(S), MP8-
II, FTP
3 Installation
Remarks
The length is
determined based
on the pre-sales
engineering survey.
If a five-core cable
is used, the neutral
wire is not used
and should be
insulated.
The length is
determined based
on the pre-sales
engineering survey.
If a five-core cable
is used, the neutral
wire is not used
and should be
insulated.
The length is
determined based
on engineering
survey.
The length is
determined based
on engineering
survey.