Optional) Setting Teamwork Parameters - Huawei NetCol8000-C070 User Manual

Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0~500 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 4-6 Parameter description
Parameter
Indoor fan control type
Indoor fan silent mode
Air-side difference
pressure sensor type
Min indoor fan speed
Max indoor fan speed
----End

4.5.3 (Optional) Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Issue 09 (2022-12-15)
Teamwork group No.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork control groups can be set (1–4).
System address: The address (configurable range: 1–32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data. The recommended value range is 1 to the number of
units in the group.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Sets the control type for
the indoor fan.
Set maximum speed of
indoor fan to reduce
equipment noise.
Sets the measuring
range for the air side
differential pressure
sensor.
Sets the minimum speed
for the indoor fan.
Sets the maximum speed
for the indoor fan.
4 Power-On Commissioning
Configuration Principle
Normally, retain R/S air
temp diff rate ctrl. If
the differential pressure
sensors are configured,
change to Pressure diff
ctrl.
You are advised not to
change the value.
There is no default value.
Set it to 0~500 Pa.
The default value is 60%.
You are advised not to
change the value.
The default value is
100%. You are advised
not to change the value.
110