Parameter
Temperature setpoint
Humidity setpoint
Return air sensor
Cold aisle sensor
Hot aisle sensor
The relationship between the temperature setpoint and the humidity setpoint is as
follows: Under the condition that the absolute humidity range is [0.0026, 0.0141]
for the default temperature setpoint 23°C and relative humidity range [15% RH,
80% RH], ensure that the absolute humidity range is [0.0026, 0.0141] when you
set the temperature setpoint and humidity setpoint.
Table 4-5 Setting example
Temperature Setpoint
(°C)
15
16
17
18
19
20
21
22
23
24
Issue 09 (2022-12-15)
Description
After the temperature and humidity control type and
the temperature value under this type are set, the
device performs regulation based on the settings.
● Return air: The value ranges from 18°C to 45°C.
● Supply air: The value ranges from 15°C to 35°C.
● Cold aisle: The value ranges from 15°C to 35°C.
● Hot aisle: The value ranges from 18°C to 45°C.
After the temperature and humidity control type and
the humidity value under this type are set, the device
performs regulation based on the settings.
40%–60% is recommended.
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Lower Limit of
Humidity Setpoint (%
RH)
24.7
23.1
21.7
20.4
19.2
18
16.9
15.9
15
15
4 Power-On Commissioning
Upper Limit of
Humidity Setpoint (%
RH)
80
80
80
80
80
80
80
80
80
75.3
108