How To Commission Single Component - Huawei NetCol8000-C070 User Manual

Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Be careful when configuring alarms. Only professional maintenance personnel can
change alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
is displayed.
Figure 7-17 Setting alarm parameters (1)
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
Figure 7-18 Setting alarm parameters (2)
----End

7.4.14 How to Commission Single Component

Context
Issue 09 (2022-12-15)
NO TICE
On the diagnostic mode screen, you can turn on or off components, and
control their output ratio.
If you need to manually turn on or off system components in diagnostic
mode, ensure that the smart cooling product is started before operation.
Take commissioning the indoor fan as an example.
Copyright © Huawei Digital Power Technologies Co., Ltd.
, as shown in
Figure
7-18.
7 FAQ
Figure 7-17
185