NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
3.1 Application Conditions
● If the water inlet temperature exceeds 10°C or the total load is less than 30%
of the cooling capacity of a single smart cooling product, the humidity may be
high. The customer is advised to add a dehumidifier (engineering
procurement).
● Do not install the smart cooling product near a noise-sensitive place such as an
office or a conference room.
Pipe Ports
The following table describes the ports reserved on the device.
Table 3-1 Pipe ports
Item
Water outlet
pipe
Water inlet pipe
(Optional)
Humidifier water
inlet pipe
Drainpipe
Issue 06 (2022-12-15)
3
NO TICE
NetCol5000-C065
G 1–1/2 inch internal thread
connector
G 1–1/2 inch internal thread
connector
G 3/4 inch external thread
connector
BSPP 1/2 inch internal thread
connector
Copyright © Huawei Digital Power Technologies Co., Ltd.
Product Specifications
NetCol5000-C030/C032
G 1 inch internal thread
connector
G 1 inch internal thread
connector
G 3/4 inch external thread
connector
BSPP 1/2 inch internal
thread connector
3 Product Specifications
29