NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Figure 7-5 Replacing a wet film humidifier (NetCol5000-C065)
Figure 7-6 Replacing a wet film humidifier (NetCol5000-C030/C032)
Step 4 Remove the hose clamp and remove the water inlet pipe.
Step 5 Draw out the old wet film humidifier.
Step 6 Install the new wet film humidifier by performing
After the replacement is complete, properly install the water inlet pipes to the wet
film humidifier. Ensure that the water inlet pipes are secured without leakage
risks.
Issue 06 (2022-12-15)
NO TE
For the NetCol5000-C030/C032, remove the butterfly nut and sheet metal fastener.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 System Operation and Maintenance
Step 4
to
Step
1.
143