Huawei NetCol5000-C030 User Manual page 108

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Menu
T/H Sensor
Issue 06 (2022-12-15)
Parameter
Floor water
overflow alarm
action
In-cabinet water
overflow alarm
action
Temperature and
humidity control
type
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On Commissioning
Description
Set the action of the device if there is water
overflow on the floor based on the actual
scenario.
● Shutdown: The device shuts down when
a floor water overflow alarm is
generated.
● Inactivity: The device runs as usual when
a floor water overflow alarm is
generated.
● Only indoor fan running: Only the indoor
fan runs when a floor water overflow
alarm is generated.
● Humidifier stopped: Only the humidifier
is stopped when a floor water overflow
alarm is generated.
Set the action of the device if there is water
overflow in the cabinet based on the actual
scenario.
● Shutdown: The device shuts down when
an in-cabinet water overflow alarm is
generated.
● Inactivity: The device runs as usual when
an in-cabinet water overflow alarm is
generated.
● Only indoor fan running: Only the indoor
fan runs when an in-cabinet water
overflow alarm is generated.
● Humidifier stopped: Only the humidifier
is stopped when an in-cabinet water
overflow alarm is generated.
When the application scenario is non-aisle
containment, you are advised to choose
Return air. Choose Cold aisle if cold aisle
T/H sensors are installed. Hot aisle is not
recommended.