Bypass Contactor; Main Contactor; Circuit Breaker; Power Factor Correction - GE ASTAT XL User Manual

Table of Contents

Advertisement

6.1.7
Inside delta installation, non-bypassed
K1
CAUTION
When connecting the ASTAT XL in inside delta configuration, always install a main contactor or
shunt trip circuit breaker.
6.2

Bypass Contactor

Some ASTAT XL soft starters are internally bypassed and do not require an external bypass contactor.
Non-bypassed soft starters may be installed with an external bypass contactor. Select a contactor
with an AC1 rating greater than or equal to the full load current rating of the connected motor.
6.3

Main Contactor

A main contactor must be installed if the ASTAT XL is connected to the motor in inside delta format and
is optional for in-line connection. Select a contactor with an AC3 rating greater than or equal to the
full load current rating of the connected motor.
6.4

Circuit Breaker

A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the
event of a soft starter trip. The shunt trip mechanism must be powered from the supply side of the
circuit breaker or from a separate control supply.
6.5

Power Factor Correction

If power factor correction is used, a dedicated contactor should be used to switch in the capacitors.
CAUTION
Power factor correction capacitors must be connected to the input side of the soft starter.
Connecting power factor correction capacitors to the output side will damage the soft starter.
6.6

Earth Terminals

Earth terminals are located at the back of the soft starter.
• QLxxB0023D ~ QLxxB0105D have one terminal on the input side (top).
• QLxxB0145D ~ QLxxB1000D and QLxxX0255D ~ QLxxX1600D have two terminals, one on the input
side (top) and one on the output side (bottom).
6.7

Power Supply Fuses

Semiconductor fuses can be used for Type 2 coordination (according to IEC 60947-4-2 standard) and to
reduce the risk of damage to SCRs from transient overload currents.
HRC fuses (such as Ferraz/Mersen AJT fuses) can be used for Type 1 coordination according to IEC
60947-4-2 standard.
CAUTION
Adaptive Control controls the motor's speed profile, within the programmed time limit. This
may result in a higher level of current than traditional control methods.
For applications using Adaptive Control to soft stop the motor with stop times greater than 30 seconds,
motor branch protection should be selected as follows:
• standard HRC line fuses: minimum 150% motor full load current
• motor rated line fuses: minimum rating 100/150% motor full load current
• motor control circuit breaker minimum long time setting: 150% motor full load current
• motor control circuit breaker minimum short time setting: 400% motor full load current for 30
seconds
ASTAT XL User Manual
F1
1/L1
2/T1
3/L2
4/T2
V1(2)
W1(3)
5/L3
6/T3
13
14
K1
DET-812
K1
F1
U1(1) U2(4)
M
V2(5)
3
W2(6)
Fout! Stijl niet gedefinieerd.
Main contactor (strongly
recommended)
Semiconductor fuses (optional)
25

Advertisement

Table of Contents
loading

Table of Contents