Parameter Descriptions

8.4.1
1 Motor Details
NOTE
Parameter 1B determines the trip current for motor overload protection. The default setting
of parameter 1B provides Motor Overload Protection: Class 10, Trip Current 105% of FLA (full
load amperage) or equivalent.
1A – Motor FLC
Range:
Description:
1B – Locked Rotor Time
Range:
Description:
1C – Motor FLC-2
Range:
Description:
1D – Locked Rotor Time-2
Range:
Description:
1E – Dual Thermal Model
Options:
Description:
ASTAT XL User Manual
Model dependent
Matches the starter to the connected motor's full load current. Set to the full
load current (FLC) rating shown on the motor nameplate.
0:01 - 2:00 (minutes:seconds)
Sets the maximum length of time the motor can sustain locked rotor current
from cold before reaching its maximum temperature. Set according to the
motor datasheet.
Model dependent
Sets the secondary motor's full load current.
0:01 - 2:00 (minutes:seconds)
Sets the maximum length of time the motor can sustain locked rotor current
from cold before reaching its maximum temperature. Set according to the
motor datasheet.
Single (default)
Dual
Activates dual thermal modelling. The dual thermal model is required only if
the ASTAT XL is controlling two physically separate motors.
DET-812
Fout! Stijl niet gedefinieerd.
Default Setting
00:01 mm:ss
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Trip Starter
Default: 10 seconds
Default: 10 seconds
41