7

Operation

7.1

The Keypad

1
2
Hand
Hand
Auto
3
4
5
Exi t
6
7.2

Starter Status LEDs

LED name
On
Ready
The motor is stopped and the starter is
ready to start.
Run
The motor is in run state (receiving full
voltage).
Alarm
The starter has tripped.
Hand
The starter is in Local control mode.
Status
The status screens are active.
Graph
The graph screens are active.
Alarm Logs
The logs menu is open.
If the starter is in remote control mode, the Hand LED will be off.
If all LEDs are off, the starter is not receiving control voltage.
7.3

Displays

The keypad displays a wide range of performance information about the soft starter.
half of the screen shows real-time information on current or motor power (as selected in parameter
10J). Use the STATUS button or
of the screen.
• Starter status
• Motor temperature
• Current
• Motor power
• Last start information
• Date and time
• SCR conduction
ASTAT XL User Manual
1
2
Alarm
Status
Graph
Logs
3
Start
Ready
Stop
Run
4
Reset
Alarm
5
Menu
Enter
6
and
Four-line display for status and programming details.
HAND/AUTO: Toggle between Hand and Auto control (i.e.
local/remote control mode)
STATUS: Open the status displays and scroll between different
status screens
GRAPH: Open the performance graphs and scroll between different
graph screens
ALARM LOGS: Open the logs
Soft starter local control buttons:
START: Start the motor
STOP: Stop the motor
RESET: Reset a trip (Hand mode only).
Status LEDs (see below for details)
Menu navigation buttons:
EXIT: Exit the menu or parameter, or cancel a parameter change.
ENTER: Enter a menu or parameter, or save a parameter change.
: Scroll to the next or previous menu or parameter, change
the setting of the current parameter or scroll through the status or
graph screens.
Remote input LEDs. When on:
INPUT A: Programmable input A is active
START: The remote start input is active
STOP: The remote stop input is active
RESET: The remote reset input is active
Flashing
The motor is stopped and the starter is
waiting for the Restart Delay (parameter 5A)
or Motor Temperature Check (parameter 4F).
The motor is starting or stopping.
The starter is in warning state.
The graph has been paused.
buttons to select the information shown on the top half
DET-812
Fout! Stijl niet gedefinieerd.
The bottom