Power Terminations - GE ASTAT XL User Manual

Table of Contents

Advertisement

5.6

Power Terminations

NOTE
For personnel safety, the power terminals on models up to QLxxB0105D are protected by
snap-off tabs. When using large cables, it may be necessary to break off these tabs.
NOTE
Some units use aluminium busbars. When connecting power terminations, we recommend
cleaning the surface contact area thoroughly (using an emery or stainless steel brush) and
using an appropriate jointing compound to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 ºC or higher.
Cable size:
6-50 mm
10-1/0)
Torque: 4 Nm (2.9 ft-lb)
QLxxB0145D
19 Nm (14.0 ft-lb)
8.5 mm
(M8)
19 mm
QLxxB0350D~QLxxB0425D
38 Nm (28.0 ft-lb)
11 mm
(M10)
28 mm
QLxxX0360D~QLxxX0930D
38 Nm (28.0 ft-lb)
10.5 mm
(M10)
18
ASTAT XL User Manual
QLxxB0023D~QLxxB0105D
2
(AWG
14 mm (0.55 inch)
QLxxB0170D~QLxxB0220D
38 Nm (28.0 ft-lb)
10.5 mm
(M10)
6 mm
QLxxB0500D~QLxxB1000D
38 Nm (28.0 ft-lb)
11 mm
(M10)
6 mm
32 mm
13 mm
DET-812
19 mm
6 mm
10.5 mm
(M10)
13 mm
32 mm
QLxxX1200D~QLxxX1600D
66 Nm (48.7 ft-lb)
12.5 mm
(M12)
51 mm
Fout! Stijl niet gedefinieerd.
Torx T20 x 150
Flat 7 mm x 150
QLxxB0255D
38 Nm (28.0 ft-lb)
11 mm
(M10)
5 mm
28 mm
QLxxX0255D
38 Nm (28.0 ft-lb)
6 mm
32 mm
16 mm