Mitsubishi Electric AJ65VBTCU-68DAVN User Manual page 30

Digital-analog converter module
Hide thumbs Also See for AJ65VBTCU-68DAVN:
Table of Contents

Advertisement

Available languages

Available languages

(2) Checking the plug cover
Check whether the plug cover is installed in the plug.
Plug cover
Plug body
Metal contact
(3) Inserting the cable
Lift the back of the plug cover and insert the
cable until it makes contact with the plug.
Insert the signal cables into the one-touch
connector plug as shown below.
<For
communication>
5 4 3 2 1
Point
• Insert the cables far enough.
Not doing so can cause an insulation displacement fault.
• The cable inserted may come out of the cover front.
At this time, pull it back until the cable tip goes back into the plug cover.
(4) Insulation displacement of plug cover
Using pliers or like, push the plug cover into the plug
to insulation-displace it.
After insulation displacement, make sure that the plug
cover is securely installed in the plug as shown below.
Point
• The plug cover and plug latches may not engage at the time of
insulation displacement, raising the cover. Since the plug cover has not
been insulation-displaced sufficiently in this state, push the cover into
the plug until it is installed securely.
Caution:
Before inserting the cable, do not push the
plug cover into the plug. Once insulation-
displaced, the plug cannot be reused.
<For power supply
and FG>
5 4 3 2 1
Signal name
DA (Blue)
DB (White)
DG (Yellow)
NC
SLD
16
<For analog output>
4 3 2 1
Signal name
FG
+24V (UNIT)
24G (UNIT)
NC
NC
Signal name
V+
COM

Advertisement

Table of Contents
loading

This manual is also suitable for:

13jp20

Table of Contents