Mitsubishi Electric AJ65VBTCU-68DAVN User Manual page 19

Digital-analog converter module
Hide thumbs Also See for AJ65VBTCU-68DAVN:
Table of Contents

Advertisement

Available languages

Available languages

Name and
No.
appearance
POWER
RUN
Operation
1)
status display
LED
L RUN
L ERR.
TEST
Offset/gain
CH
2)
adjusting LEDs
OFFSET
GAIN
SELECT/SET
3)
The switch to be used for making the offset/gain settings during test mode.
switch
UP/DOWN
Used to adjust the offset value and gain value of the channel specified by the
4)
switch
SELECT/SET switch.
The switch to be used for selecting the mode among Ver. remote device station (Ver.-
compatible slave station)/Normal mode/Test mode
Mode select
switch
5)
(Factory-set to
"0")
ON
: Power supply on
OFF : Power supply off
On
Flickering: 0.1s intervals: Output range setting error, mode select
Normal
mode
Off
On
Flickering: 0.1s intervals: Mode select switch setting error
Test
mode
Off
On
: Normal communication
Off
: Communication cutoff (time expiration error)
On
: Indicates that transmission speed setting or station number setting is
outside the range.
Flicker at fixed intervals:Indicates that transmission speed setting or station
number setting was changed from that at power-on.
Flicker at unfixed intervals:Indicates that you forgot fitting the terminating
resistor or the module or CC-Link dedicated cable is affected by noise.
Off
: Indicates normal communications.
Normal
Normally OFF.
mode
TEST : ON
Test
The OFFSET/GAIN/ CH LEDs lit change every time the
mode
SELECT/SET switch is moved to SELECT.
Ver.1 remote device station
(Ver.1-compatible slave station)
Ver.2 remote device station
(Ver.2-compatible slave station)
-
Description
: Normal operation
switch setting error. This module is used as the Ver.2 remote
device station (Ver.2 compatible slave station) when the
network parameter mode is set to remote network Ver.1
mode.
0.5s intervals: Average value setting (count) time error.
Mode select switch setting is changed after power-on.
:24VDC power supply shutoff or watchdog timer error
occurred.
: Indicate that the SELECT/SET switch is in the SET
position.
0.5s intervals: An attempt was made to make setting outside
the setting range at the time of offset/gain setting.
: Indicates that the SELECT/SET switch is in the SELECT or
center position.
AJ65VBTCU-68DAVN
0: Normal mode
1: Test mode (User range setting 1)
2: Test mode (User range setting 2)
3: Normal mode
4: Test mode (User range setting 1)
5: Test mode (User range setting 2)
6 to 7: Use prohibited
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

13jp20

Table of Contents