9.2
9.2.1
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
the General control cabinet 4590, in which three Fan control
panels 4593 can be mounted. For connection to the c.i.e. is one
I/O Matrix board 4582 required for each 4594 board. Each
4594 board is connected to a COM loop and 24 V DC. Up to
eight 4593 panels can be used (i.e. sixteen 4594 with 4582).
One I/O unit 3361 is also required for each fan. For more
information, see Technical Description MEW01245.

Units connected to the RS485 interface

NOTE! In a mixed system
has to be added in the Site Specific Data (SSD), in spite this board is
not used physically.
Up to sixteen Display Units type Ext. FBPs (1826 / 1828) and/or Alert
Annunciation Units (1735 / 1736) and/or Ext. Presentation Units
(1728) can be connected to the built-in RS485 interface (J4:37-38) in
EBL512 G3. Note that the current consumption for 1826 with printer
can be up to 200 mA when printing. (Power supply at J4:35-36.)
Connections, see drawing 512 G3 – 24.
NOTE! Display Unit software version > 1.4.1 is required.
Address and S/W mode settings
The display and the push buttons (in the unit respectively) are used to
set the address, which also can be changed via EBL512 G3. The S/W
mode shall be set to xxxx – 1587 (xxxx = type number). See the
Technical Description for the unit respectively.
The first unit shall have the address 00, the second unit address 01 and
45
so on
. Follow the Address setting instructions in the Technical
Description for the unit respectively.
Via Win512 version 2.7.x can "Selective alarm presentation" be
programmed, i.e. you can select which alarms that shall be presented
in each unit, see the Technical Description for the unit respectively.

External Fire Brigade Panels

1826 External Fire Brigade Panel (ext. FBP). A light grey metal
housing (HxWxD, 288 x 400 x 95 mm) with a door. A key is
required to open the door, which has a Plexiglas ahead of the
FBP front. It has cable inlets on the top, bottom and back sides
and is intended to be wall mounted. Two compression glands
are attached.
LED indicators and push buttons on the front are like the upper
black part of the EBL128 / 512 front. The front's designation
texts are in Swedish. A neutral front is available, where the
designation texts, in any language, are made separately and by
44
EBL512 G3, S/W United version 2.7.x.
45
The connection order on the line is not dependent of the address.
44
one 1587 Ext.FBP/DU interface board