User manual MEW01603 Revision - Fire alarm system EBL512 G3 EBL512 G3 version 2.0.x Daily user's manual Author: Jan Pettersson Date of issue: 2013-01-10 Date of rev:...
Page 2
This page has deliberately been left blank.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Table of contents Introduction________________________________ 2 Front______________________________________ 3 Log on to the Control Unit (c.i.e.) ______________ 4 Perform monthly test (H1) ___________________ 6 Disable or re-enable (H2) ____________________ 7...
Due to continual development and improvement different S/W versions can be found. This document is valid for EBL512 G3 S/W version 2.0.x. (x=0 at the "Date of issue" or "Date of revision".) The document describes the main menus (incl. the sub menus) valid for access level / type "Building officer".
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Log on to the Control Unit (c.i.e.) User name Up to ten (10) User names (0, 1, 2 - - 9) might be programmed. Default are normally three User names available (0, 1 and 2) but they might have been changed and/or User names 3 –...
Page 7
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Building officer (Described in this document.) H1 Perform monthly test H2 Disable or re-enable H3 Set calendar and clock H4 Present system status H6 FAULT Acknowledge...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Perform monthly test (H1) Not possible for access level / type "Information only". Menu Press the Soft key "Menu". With the keypad select 0, 1, 2 - - 8 or 9 for a User name.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Disable or re-enable (H2) Not possible for access level / type "Information only". NOTE! One or more disablements in the system are indicated by the LED "General disablements"...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Zone or Zone / Address (B1) Up to 512 whole zones can be disabled via menu B1. Normally all alarm points within the zone will be disabled except the addressable manual call points.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Output (B2) Up to 200 outputs can be individually disabled via menu B2. Cont. from , page 7. B1 Zone or Zone / Address ...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Output type (B3) Outputs of the same type can be collectively disabled via menu B3. Cont. from , page 7. B1 Zone or Zone / Address ...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Alarm devices (B4) Outputs of the type "Alarm devices" can be collectively disabled via menu B4. Cont. from , page 7. B1 Zone or Zone / Address ...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Routing equipment (B5) Outputs for routing equipment (fire alarm and fault condition respectively) can be disabled via menu B5. Cont. from , page 7.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Alert Annunciation function (B6) The Alert Annunciation function can be permanently turned off via menu B6 – until turned on again via menu B6. The LED "Fire brigade tx delay" on the front is indicating when the alert annunciation function is turned on, i.e.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Set calendar and clock (H3) The time, date and day set via this menu will be valid for the whole system. NOTE! If you don't want to change anything in menu H3, press ESC to leave the menu.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Present system status (H4) If the c.i.e. has a printer it is possible to get a print-out from some of the sub menus U1-U8. Print If it is possible to get a print-out, the Soft key "Print"...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Disablement (U1) Disablements, except disablements by time channel, will be displayed via menu U1, also alarm points that have been automatically disabled in conjunction with fire alarm reset.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Open doors (U3) If any door in the system is open, the open door symbol is shown up to the right in the display's symbol area.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Sensors activating SERVICE signal (U5) If any smoke detector in the system is activating SERVICE signal, the SERVICE signal symbol is shown up to the right in the display's symbol area.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Event log (U7) Three types of event logs are available. Up to 999 events per log. Cont. from , page 15. U1 Disablement ...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual FAULT Acknowledge (H6) LED "Fault tx activated" on the front (down to the left) is indicating that the output for Fault condition routing equipment is activated.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Perform ZONE TEST (Test mode) (H7) Up to 100 zones can be set in test mode, which is indicated by the LED "Test mode" on the front.
Page 24
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual ⓫ Press ( ). A successful ending of test mode for a zone is indicated by a beep and it will also disappear from the End test mode list ⓬...
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Interlocking outputs and inputs (H9) Menu Press the Soft key "Menu". With the keypad select 0, 1, 2 - - 8 or 9 for a User name.
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual 10.1 Activated interlocking outputs / inputs (C1) Cont. from ➏, page 23. C1 Activated interlocking outputs / inputs Press ( ). This is a list, i.e. you can scroll in the list with ( ) or ( ).
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual ⓭ Press ( ). A successful deactivation is indicated by a beep and the output will also disappear from the Deactivate list ⓮ To leave a menu press ESC To leave the menu system press the Soft key "Escape menu".
Panasonic Eco Solutions Nordic AB MEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual Change password (H10) You can change the Password for the User name that was used for log on to the control unit. An incorrect password will result in no change.