Panasonic EBL512 G3 Planning Instructions page 140

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
21.6.2
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
2300
(ION)
Offset,
10
Pre-warning
Offset,
18
Fire alarm
Offset,
22
Heavy smoke
Sampling
2
interval
NOTE! If any of these values are changed it might be a violation
to the EN54-2 standard.
Sampling interval:
1 = 3 values over alarm level to activate alarm.
2 = 5 values over alarm level to activate alarm.
3 = 7 values over alarm level to activate alarm.
Heat detectors' (3308, 3309, 3316 and 4300) properties
Detector:
3308(AHD), also valid for 3309
3316 / 4300 HEAT (AMD), i.e. the heat detector part
when decision algorithm is not selected.
Logical name: Class A1, Class A2 (S) or Class B (S).
Short name: A1, A2 or B
Algorithm parameters: Default values, see table:
3308 (3309)
(AHD)
A1
A2
Level,
92
100
Pre-warning
Level,
112
120
Fire alarm
Level,
180
180
Heavy alarm
Rise
8
A
time
Step
20
A
down
NOTE! If any of these values are changed it might be a violation
to the EN54-2 standard.
A
Rate-of-rise > 8 x 0.5 = 4° C per minute gives an alarm level
temperature step down of 20 x 0.5 = 10° C
138
2210
2304
(ION2)
(OPT)
(OPT2)
20
10
35
13
45
22
2
3
3316 / 4300 HEAT
(AMD)
B
A1
A2
B
128
46
50
64
148
56
60
74
180
90
90
90
4
10
2210
AUT
20
45
25
60
45
100
3
1
For 3308 (3309)
x 0.5° C
x 0.5° C
x 0.5° C
x 0.5° C per min.
x 0.5° C