Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Checkbox not marked = Reset of fan control system is global, i.e.
all fan control systems in the system will be reset. (Fan control,
see page 33.)

LCD in quiescent state

Bottom row: The text to be shown on in the LCD in all control units
in the system, when the system is in quiescent state, e.g. the name of
the installation. Max. 40 characters. (In EBL512 G3 United version
2.7.x the text will be automatically centred.)

Time channels

The control unit RTC (real time clock) controls time channels 1-14.
Time channels can be used to:
disable and re-enable alarm points
set alert annunciation ON / OFF
activate programmable control outputs
set alternative alarm algorithm for analog detector types 33xx
/430x ON / OFF
set 2-unit dependence function ON / OFF
The properties for each Time channel (1-14) and each Day of the
week (1-8) have to be set for the channels that shall be used.
Figure 31. Properties for one time channel and one day. Day
of week 1 = Monday. Day of week 8 = National holiday.
 = On.
On = Off.
All (52) weeks of a year have the same settings. When a national
holiday appears in the middle of a week, separate ON/OFF times can
be set for that holiday, i.e. the day of the week = 8. The National
holiday dates have to be set separately in the "National holidays" tab.

Time activation output

See also chapter "Time Activation Output", page 68.