Enclosure, modular enclosure, modular enclosure for 6u configuration and thinksystem sd530 compute node messages and codes reference
Hide thumbs Also See for ThinkSystem D2:
Table of Contents

Advertisement

1. If warning is not de-asserted after several minutes, check all five fans are installed.
2. Reseat fan module a couple of times. If error still persist, replace fan module.
• 04010210: FAN_TACH_1A: Fan sensor, critical event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when Fan tach reading is below error threshold RPM.
Severity: Critical
User Action:
1. If critical is not de-asserted after several minutes, check all five fans are installed.
2. Reseat fan module a couple of times. If error still persist, replace fan module.
• 04010211: FAN_TACH_1B: Fan sensor, critical event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when Fan tach reading is below error threshold RPM.
Severity: Critical
User Action:
1. If critical is not de-asserted after several minutes, check all five fans are installed.
2. Reseat fan module a couple of times. If error still persist, replace fan module.
• 04010212: FAN_TACH_2A: Fan sensor, critical event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when Fan tach reading is below error threshold RPM.
Severity: Critical
User Action:
1. If critical is not de-asserted after several minutes, check all five fans are installed.
2. Reseat fan module a couple of times. If error still persist, replace fan module.
• 04010213: FAN_TACH_2B: Fan sensor, critical event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when Fan tach reading is below error threshold RPM.
Severity: Critical
User Action:
1. If critical is not de-asserted after several minutes, check all five fans are installed.
2. Reseat fan module a couple of times. If error still persist, replace fan module.
• 04010214: FAN_TACH_3A: Fan sensor, critical event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when Fan tach reading is below error threshold RPM.
Severity: Critical
User Action:
1. If critical is not de-asserted after several minutes, check all five fans are installed.
2. Reseat fan module a couple of times. If error still persist, replace fan module.
• 04010215: FAN_TACH_3B: Fan sensor, critical event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when Fan tach reading is below error threshold RPM.
10
ThinkSystem D2 Enclosure, Modular Enclosure, Modular Enclosure for 6U Configuration and ThinkSystem SD530 Compute Node
Messages and Codes Reference