Parameter setting example:

"Changing valve action from direct to reverse"
Starting situation: the TZID-C is operating on the operating level in an arbitrary mode.
1. Change over to the configuration level:
-
Simultaneously press and hold
-
In addition, briefly press
-
Wait until countdown from 3 to 0 has run down.
-
Release
ENTER
-
conf
2. Change over to parameter group 2._ (See "Parameter group 2: Setpoint" on page 57):
-
Simultaneously press and hold
-
In addition briefly press
-
conf
-
Release
MODE
-
conf
3. Select parameter 2.3 "Valve action:
-
Press and hold
-
In addition, 3 x briefly press
-
conf
-
Release
MODE
4. Change parameter setting:
-
Briefly press
e
ENTER
.
°
C
%
is displayed.
mA
MODE
once.
°
C
%
mA
is displayed.
.
and
ENTER
°
C
%
is displayed.
mA
.
MODE
.
°
C
%
is displayed.
mA
.
to select "REVERSE".
Brief operating instructions
and
.
.
and
ENTER
Brief operating instructions
.
42/18-64-4 EN