Table 7-3 Fire alarm control panel specifications
Item
AC input power
AC input voltage
DC backup
power
Capacity
Wire system of the detector loop
Length of the detector loop
Relay contact capacity
Output loop current limiting for the
electromagnetic valve
Output loop current limit for other
drivers

7.3.2 Heptafluoropropane Automatic Fire Extinguisher

When the FusionDC1000 catches fire, a lot of smoke is generated and the
temperature rises sharply. The smoke detector and heat detector send fire alarm
signals to the fire alarm control panel, which generates an electromagnetic valve
start voltage to start the electromagnetic valve of the fire cylinder. Then the fire
cylinder valve is opened, and extinguishant is released into the protected zone.
Issue 01 (2021-04-20)
Provides a signal input port for gas release confirmation (onsite pressure
feedback). The gas release confirmation mode can be set by users. There are
two modes available: onsite pressure feedback and electromagnetic valve
drive.
Allows the system to identify states such as fault, fire alarm, and gas release,
and provides the gas release indicator drive, fire alarm horn/strobe drive, and
alarm bell drive.
Provides the single-point test function for detectors, making the working
status and test data of detectors intuitive.
Allows you to set the working status of the area control unit to manual or
automatic.
Provides a 4.3-inch color LCD, and working status printer.
Voltage
Electrical energy
Number of detector
loops
Number of detectors
connected to each
loop
Copyright © Huawei Technologies Co., Ltd.
7 Fire Extinguishing System
Specifications
≤ 120 W
220 V AC±20%
24 V DC
7.0 Ah
Two loops: one loop connected to the
common heat detector and the other
connected to the smoke detector
≤ 20 (common detectors)
Two-wire system
≤ 1000 m
7 A, 24 V DC for all relays
≤ 3 A
≤ 1 A