Optional) Heptafluoropropane Fire Extinguisher - Huawei FusionModule1000A20 Product Description

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One Data
Center
Product Description (380 V)
Table 3-35 Extinguishant control panel specifications
Item
Input
24 V power output
Capacity
Output loop current
limiting

3.5.3 (Optional) Heptafluoropropane Fire Extinguisher

When the FusionModule1000 catches fire, a lot of smoke is generated and the temperature
rises sharply. The smoke detector and heat detector send fire alarm signals to the
extinguishant control panel, which generates an electrical actuator start voltage to start the
electrical actuator of the fire cylinder. Then the fire cylinder valve is opened, and
extinguishant is released into the protected zone.
Heptafluoropropane (HFC-227ea) is a colorless, odorless, non-conductive, and secondary
pollution-free gas extinguishant. It features cleanness, low toxicity, good electrical insulation,
high fire extinguishing efficiency, zero threat to the ozonosphere (ODP = 0), and short
residual time (ATL = 34Y).
Issue 01 (2019-10-31)
Number of
detection
loops
Number of
detectors
connected
to each
loop
The extinguishant control panel is equipped with two 12 V batteries and the required cables.
Copyright © Huawei Technologies Co., Ltd.
Specifications
AC input frequency: ≤ 120 W
AC input voltage and frequency: 230 V AC (tolerance ±10%),
50 Hz
DC backup power voltage: 24 V DC
3 A
Three loops. Loops 1 and 2 respectively connect to smoke
detectors and heat detectors. Loop 3 is reserved by default.
≤ 24 PCS
Output loop for the solenoid valve driver: 1 A
Output loops for other drivers: 1 A
3 System Architecture
64

Advertisement

Table of Contents
loading

Table of Contents