FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
Item
Altitude
Physical Ports
Table 5-3 Physical ports
Item
Refrigerant liquid pipe
Refrigerant gas pipe
Humidifier water inlet pipe
Top drainage port
Bottom drainage port
Installation Requirements
Table 5-4 Installation requirements
Item
Room door
Floor
Installation mode
Pipe and cable routing
Equivalent length of the
one-way pipe
Vertical distance between
the indoor and outdoor
units
Thermal insulation foam
thickness
Issue 01 (2021-04-20)
Specifications
0–4000 m, derated at above 1000 m. For details about derating
data, contact Huawei technical support.
Specifications
Copper pipe; outer diameter: 5/8 inch (15.88 mm); wall thickness:
1.0 mm; pressure withstanding capacity ≥ 4.5 MPa; welded
Copper pipe; outer diameter: 3/4 inch (19.05 mm); wall thickness:
1.0 mm; pressure withstanding capacity ≥ 4.5 MPa; welded
Reserved port: G 1/2 inch, port with inner threads
Reserved port: BSPP 1/2 inch; thread connection
Reserved port: copper pipe with an outer diameter of 5/8 inch. A
hose with the inner diameter of 14 mm is recommended.
Specifications
Width ≥ 1.2 m; height ≥ 2.3 m
Bearing capacity ≥ 530 kg/m
Installed on a concrete floor, a base, or an ESD floor
Top or bottom routing
≤ 100 m
● If the outdoor unit is placed higher than the indoor unit, the
vertical distance between them should be less than or equal to
30 m.
● If the indoor unit is placed higher than the outdoor unit, the
vertical distance between them should be less than or equal to 8
m.
≥ 13 mm
Copyright © Huawei Technologies Co., Ltd.
2
; height of the raised floor ≥ 250 mm
5 Cooling System
55