Tuning the second motor (Pr.463)
• When one inverter switches the operation between two different motors, set the second motor in Pr.450 Second applied
motor, set Pr.463 Second motor auto tuning setting/status = "11", and perform tuning of the second motor.
• Turning ON the RT signal enables the parameter settings for the second motor as shown in the following table.
Function
Motor constant (R1)
Frequency search gain
Auto tuning setting/status
NOTE
• To use the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the
function to an input terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.9 Electronic thermal O/L
Pr.65, Pr.67 to Pr.69 Retry
Pr.71 Applied motor, Pr.450 Second applied
Pr.79 Operation mode
selectionpage 180
Pr.156 Stall prevention operation
Pr.178 to Pr.189 (Input terminal function
372
14.(A) Application Parameters
14.9 Offline auto tuning for a frequency search
Pr.458
Pr.560
Pr.463
relaypage 206
functionpage 216
motorpage 304
selectionpage 222
selection)page 292
RT signal ON (second motor)
RT signal OFF (first motor)
Pr.90
Pr.298
Pr.96