Mitsubishi Electric 800 Series Instruction Manual page 292

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Adjustment by changing the torque without adjusting the current (voltage) (Example of
changing the gain torque from 150% to 130%)
Operating procedure
1.
Selecting the parameter
Turn the setting dial or press the UP/DOWN key until "C40" (Pr.933) appears.
Press the SET key to show the present set value. (150.0%)
2.
Torque setting change
Turn the setting dial or press the UP/DOWN key to change the value to "130.0". (130.0%)
Press the SET key to confirm the setting. "130.0" blinks.
3.
Selecting the mode and the monitor item
Press the MODE key three times to select the monitor mode and to monitor a frequency.
4.
Start
Turn ON the start switch (STF or STR) to apply a voltage across terminals 4 and 5.
Operation is performed with 130% torque.
NOTE
• If the current (voltage) values at the gain and bias torques are too close to each other, an error ("Er3") may be indicated.
• Use the calibration parameter C38 (Pr.932) to set the bias torque. (Refer to
CAUTION
• When setting a value other than "0" as the bias torque, note that simply turning ON the start signal will supply torque to
the motor even if a torque command is not given.
Parameters referred to
Pr.20 Acceleration/deceleration reference
Pr.267 Terminal 4 input
selectionpage 274
Pr.79 Operation mode
selectionpage 180
Pr.858 Terminal 4 function
assignmentpage 279
frequencypage 164
page
287.)
12.(T) Multi-Function Input Terminal Parameters
12.5 Torque (magnetic flux) setting current (voltage) bias and gain
11
12
13
14
15
16
17
18
19
20
291