 Adjusting the response of input terminals (Pr.699)
• Response of the input terminals (physical terminals) can be delayed in a range between 5 to 50 ms. (The following is the
operation example of the STF signal.)
ON
STF
Pr.699
9999
Pr.699
NOTE
• The Pr.699 setting is invalid (no filter) for the following signals.
— Input signals which are already in the ON state when the power is turned ON
— Input signals used for the PLC function
— Output stop (MRS) signal
Time
OFF
Pr.699
12.(T) Multi-Function Input Terminal Parameters
12.6 Input terminal function selection