Huawei FusionModule1000A40 Product Description page 82

Prefabricated all-in-one data cente
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)
The design and construction of the extinguishant control panel comply with EN 54
and EN 12094.
Figure 3-59 Extinguishant control panel
Table 3-59 Extinguishant control panel specifications
Item
Input
24 V power
output
Issue 03 (2021-02-10)
Two zones supported, a third zone configurable
Serial status connection and timer display
Hold activated indication and disablement indication
Test mode
Two first stage sounder outputs
One second-stage audible and visual alarm output
First- and second-stage relay contacts
Auxiliary 24 V DC output
Monitored manual release input and output
Monitored release pneumatic switch input
(Optional) Mode select key switch on the front panel
(Optional) Manual release on the front panel
Specifications
AC input frequency: ≤ 120 W
AC input voltage and frequency: 230 V AC (tolerance
±10%), 50 Hz
DC backup power voltage: 24 V DC
3 A
Copyright © Huawei Technologies Co., Ltd.
3 Architecture
76

Advertisement

Table of Contents
loading

This manual is also suitable for:

V200r003c10

Table of Contents