Huawei FusionModule1000A40 Product Description page 48

Prefabricated all-in-one data cente
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)
Figure 3-35 Low temperature component
(1) Safety valve
(4) Condensing pressure
control valve
A low temperature component is mandatory if the outdoor ambient temperature
may be below –20°C.
Table 3-19 Low temperature component specifications
Item
Heater box power supply
Heater box voltage tolerance
Heater box frequency tolerance
Refrigerant
Liquid pipe outer diameter
Gas pipe outer diameter
Dimensions (H x W x D)
Expansion bolt hole
Storage temperature
Storage humidity
Maximum operating pressure
Issue 03 (2021-02-10)
(2) Liquid line port 1
(5) Gas pipe port 1
Specifications
220 V AC to 240 V AC, 1 P, 50 Hz/60 Hz
Rated voltage ±10%
Rated frequency ±3 Hz
R410A
5/8 inch (15.9 mm)
7/8 inch (22.3 mm)
944 mm x 632 mm x 507 mm (with packing)
828 mm x 470 mm x 300 mm (without
packing)
M12x60
–40°C to +70°C
5%–95% RH (non-condensing)
4.35 MPa
Copyright © Huawei Technologies Co., Ltd.
3 Architecture
(3) Liquid line port 2
(6) Gas pipe port 2
42

Advertisement