Transferring Parameters - Mitsubishi Electric MELSEC-Q Structured Programming Manual

Hide thumbs Also See for MELSEC-Q:
Table of Contents

Advertisement

FXCPU Structured Programming Manual
[Device & Common]
Set item
Details of Execution
Click the "END" button to finish the setting and close the " Remote device station Initial Setting Procedure
Registration" dialog box.
7. Click the "END" button to finish the setting and close the "Remote Device Station Initial
Setting Target Station No. Setting" dialog box.
6.6.3
Transferring parameters (, sequence program and symbolic information
1. Select [Online]-[Write to PLC] from the tool menu to display the "Online Data Operation"
dialog box.
2. Check the "Parameter", and click the [Execute] button.
The selected contents are transferred to the PLC.
The transferred parameters become valid when the PLC mode switches from STOP to RUN.
When the communication setting is changed in the step 7 "Setting the PLC system (2)", turn OFF the power
of the PLC once, and then turn it ON again.
*1.
The Symbolic information is supported in the FX
Cautions
1) Make sure to write both the program and parameters to the PLC after changing the memory capacity
setting.
If only the parameters are written to the PLC, program errors (such as parameter error, circuit error and
syntax error) may occur in the PLC.
2) In FX
/FX
3U
When symbolic information is stored, it is deleted if the memory capacity set by parameters is changed.
After changing the memory capacity, write the symbolic information again.
302
Write Device
Select the device to which the initial setting execution contents are written.
Set the device number to which the initial setting execution contents are
written.
When "Write Device" is set to "RY"
Remote Net (Ver.1 Mode): 00 to 7FH
Device No.
Remote Net (Ver.2 Mode), Remote Net (Additional Mode): 00 to DFH
When "Write Device" is set to "RWw"
Remote Net (Ver.1 Mode): 00 to FH
Remote Net (Ver.2 Mode), Remote Net (Additional Mode): 00 to 1FH
Set the contents of the initial settings.
When "Write Device" is set to "RY"
Write Data
Select "ON" or "OFF".
When "Write Device" is set to "RWw"
0 to 65535 (DEC), 0 to FFFFH (HEX)
PLCs Ver. 3.00 or later.
3UC
6.6 Parameter setting by GX Works2
Contents of setting
/FX
PLCs Ver. 3.00 or later.
3U
3UC
6 Types and Setting of Parameters
Setting range
RY, RWw
As shown on the left
As shown on the left
*1
) to the PLC

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-lMelsec-fFx3sFx3gFx3gcFx3u ... Show all

Table of Contents