Pdu2000; Dual-Live Wire 208 V Power System; Overview - Huawei FusionModule500 Manual

Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Item
Operating temperature
Humidity
Storage and transportation
temperature
Dimensions

3.2.1.6 PDU2000

The PDU2000 is a basic socket, rather than a monitoring socket.
Table 3-7 PDU2000 technical specifications
Item
Rated current
Input frequency
Input port
Output port configuration
Rated output current
3.2.2 Dual–Live Wire 208 V Power System

3.2.2.1 Overview

The UPS supplies uninterruptible power to IT loads by means of batteries when the external
power supply fails.
Issue 01 (2017-04-20)
Specifications (3 kVA
UPS)
–5° C to +40° C
5%–95% RH
–40° C to +70° C
430 mm x 450 mm x 130
mm
Specifications (Vertically
Installed Full-Height
PDU2000)
32 A
50 Hz/60 Hz
Cord end terminal, no input
cable
IEC: 20 x C13 + 2 x C19
Chinese national standards:
20 x 10 A + 2 x 16 A
32 A
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
Specifications (6 kVA
UPS/10 kVA UPS)
–5° C to +40° C
5%–95% RH
–40° C to +70° C
430 mm x 450 mm x 130
mm
Specifications
(Horizontally Installed 1
U PDU2000)
16 A
50 Hz/60 Hz
Cord end terminal, no input
cable
IEC: 8 x C13
Chinese national standards:
seven sockets that comply
with Chinese national
standards
16 A
27