Product Description (ECC800e)

3.2.2.4 PDU5000

Figure 3-10 PDU5000
Table 3-11 PDU5000 technical specifications
Item
Maximum input current
Number of phases
input frequency
Input voltage
Output frequency
UPS input
UPS output
UPS maintenance bypass
Output branch
Maximum altitude
Operating temperature
Humidity
Storage and transportation temperature
Dimensions

3.2.2.5 PDU2000

The PDU2000 is a basic socket, rather than a monitoring socket.
Issue 01 (2017-04-20)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
63 A
Dual-live wire
60 Hz
208 V
60 Hz
2-pole 63 A circuit breaker
2-pole 63 A circuit breaker
2-pole 63 A circuit breaker
Four 1-pole 40 A circuit breakers and one
1-pole 16 A circuit breakers
4000 m
–5° C to +40° C
5%–95% RH
–40° C to +70° C
430 mm x 450 mm x 130 mm