Huawei FusionModule500 Manual page 57

Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Pin
3
4
Current Monitoring Port
Figure 3-25 Current monitoring port pins
Table 3-33 Current monitoring port pin definitions
Pin
1
2
3
4
Issue 01 (2017-04-20)
Definition
NO
COM
If the battery string is configured with the neutral wire, measure the currents of the positive and
negative battery string cables. If the battery string is not configured with the neutral wire, measure
the current of either the positive or negative battery string cable. The following uses the scenario
where the battery string is configured with the neutral wire as an example.
When a CIM manages multiple battery strings, first connect the Hall effect sensors on the positive
and negative cables of battery string 1 respectively to the corresponding ports on the CIM. Then
connect the Hall effect sensors on battery string 2 to the CIM in the same way, and so on.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Signal
Status
Descriptio
Description
n
input is
closed.
Dry contract
Open: The
output
dry contact
signal
output is
open.
Closed:
The dry
contact
output is
closed.
Definition
+12 V
–12 V
AI
GND
3 System Architecture
Initial
Remarks
Status
Open
Description
Detect the charge and
discharge currents of four
battery strings or eight
battery routes.
51

Advertisement

Table of Contents
loading

Table of Contents