FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Figure 3-2 Power distribution conceptual diagram for the 220 V single-phase scenario with the 6
kVA/10 kVA UPS
The power distribution system meets the power supply requirements of single-phase 220
V/230 V/240 V.
Table 3-2 Power distribution system technical specifications
Item
Rated power
Rated input voltage
Rated frequency
Maximum input
current
External input
power distribution
circuit breaker
UPS backup power
Issue 01 (2017-04-20)
Specifications (10
kVA UPS)
9 kW
220 V/230 V/240 V
50 Hz/60 Hz
50 A
63 A
Battery pack
(optional):
0–4 (7 Ah/240
V)
0–4 (9 Ah/240
V)
Battery:
26 Ah/12 V
40 Ah/12 V
65 Ah/12 V
100 Ah/12 V
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications (6
kVA UPS)
5.4 kW
220 V/230 V/240 V
50 Hz/60 Hz
32 A
50 A
Battery pack
(optional):
24 U cabinet:
0–2 (7 Ah/240
V)
0–2 (9 Ah/240
V)
42 U cabinet:
0–4 (7 Ah/240
V)
0–4 (9 Ah/240
V)
Battery:
26 Ah/12 V
40 Ah/12 V
65 Ah/12 V
3 System Architecture
Specifications (3
kVA UPS)
2.7 kW
220 V/230 V/240 V
50 Hz/60 Hz
19 A
32 A
Battery pack
(optional):
24 U cabinet:
0–2 (7 Ah/240
V)
0–2 (9 Ah/240
V)
42 U cabinet:
0–4 (7 Ah/240
V)
0–4 (9 Ah/240
V)
Battery:
26 Ah/12 V
40 Ah/12 V
65 Ah/12 V
22