User Guide
Figure 2-13 Monitoring port for Boolean signals
Table 2-9
Table 2-9 Valid values of Boolean signals of the voltage type
Value Range of the Input Voltage
Signal (x)
x ≤ 3 V DC
x ≥ 5 V DC
3 V DC < x < 5 V DC
Table 2-10
Table 2-10 Meanings of the terminals of the monitoring port for Boolean signals
Silkscreen
Si+ (i ranges from 1 to 32)
Si- (i ranges from 1 to 32)
Issue 13 (2009-12-30)
NOTE
The common types of Boolean signals are the dry contact point type, OC type, voltage type, and current
l
type.
All the monitoring ports for Boolean signals support Boolean signals of the dry contact point type and
l
OC type.
Ports S13 - S16 and S29 - S32 support Boolean signals of the voltage type.
l
lists the valid values of Boolean signals of the voltage type.
lists the meanings of the terminals of the monitoring port for Boolean signals.
NOTE
You can set the DIP switches SW12A, SW12B, SW24A, and SW24B to choose whether to use the
monitoring port for Boolean signals. For details, see
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Overview of the EMU
Definition
Low level
High level
Unspecified
Meaning
Positive Boolean input of port i
Negative Boolean input of port i
2.3 Internal Structure of the
EMU.
2-15