User Manual
Step 8 Click Submit.
Figure 5-11 Adding an SPD
----End

5.2.4.3 Adding a Door Status Sensor

Prerequisites
Context
A door status sensor should be connected to the AI/DI_3 port on the MUE05A4 of the
ECC500 by default. To connect the door status sensor to another port, set the port parameters
using the following method.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_3 Port Settings.
Step 3 Set AI/DI_3 Sensor to Enable.
Step 4 Click Submit.
Step 5 Set AI/DI_3 Sensor Name, for example, to Door_Sensor.
Step 6 Set AI/DI_3 Sensor Type to Door Sensor.
Step 7 Set AI/DI_3 Power Supply to On.
Step 8 Click Submit.
Issue 03 (2020-01-06)
Figure 5-11
shows the configured page.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Figure 5-12
shows the configured page.