Setting parameters
IO controller settings
Perform the following settings for the IO controller. For details, refer to the manual of the IO controller or PROFINET
configuration tool used.
■Importing the GSDML file
Import the GSDML file of the RJ71PN93 to the PROFINET configuration tool connected to the IO controller.
■Setting parameters
Write the RJ71PN93 information to the PROFINET configuration tool connected to the IO controller.
• Network overview
Item
IO controller (SIMATIC S7-1200)
IO device (RJ71PN93)
• Device overview
Module
64 Word Output_1
64 Word Output_2
64 Word Input_1
64 Word Input_2
• PLC tags
Name
Data type
recv_area_word
Word
recv_area_dword
DWord
send_area_word
Word
send_area_dword
DWord
RefreshReq
Bool
■Program example
Refer to the following.
Page 37 Program examples of IO controller
Device name
IP address
Device name
IP address
Slot
1
2
3
4
Address
%IW68
%ID196
%QW68
%QD196
%M0.0
Setting details
plc_1
192.168.3.130
rj71pn93
192.168.3.5
I address
68...195
196...323
Comment
Receive area (slot 3, unit: word)
Receive area (slot 4, unit: double-word)
Send area (slot 1, unit: word)
Send area (slot 2, unit: double-word)
Refresh request
7 COMMUNICATION EXAMPLE
7.1 Example of I/O Data Exchanges
Q address
68...195
196...323
7
33