Generator protection REG670
Version 2.2
Voltage protection
Table 70. Two step undervoltage protection UV2PTUV
Function
Operate voltage, low and high step
Absolute hysteresis
Internal blocking level, step 1 and step
2
Inverse time characteristics for step 1
and step 2, see table
191
Definite time delay, step 1 at 1.2 x U
to 0
Definite time delay, step 2 at 1.2 x U
to 0
Minimum operate time, inverse
characteristics
Operate time, start at 2 x U
Reset time, start at 0 to 2 x U
Operate time, start at 1.2 x U
Reset time, start at 0 to 1.2 x U
Critical impulse time
Impulse margin time
Hitachi Power Grids
Range or value
(1.0–100.0)% of
(0.0–50.0)% of
UBase
(1–50)% of
-
(0.00-6000.00) s
set
(0.000-60.000) s
set
(0.000–60.000) s
to 0
Min. = 15 ms
set
Max. = 30 ms
Min. = 15 ms
set
Max. = 30 ms
to 0
Min. = 5 ms
set
Max. = 25 ms
Min. = 15 ms
set
Max. = 35 ms
5 ms typically at 1.2 x U
15 ms typically
© Copyright 2017 Hitachi Power Grids. All rights reserved
M13290-1 v15
Accuracy
UBase
±0.5% of U
r
UBase
±0.5% of U
r
±0.5% of U
r
See table
191
±0.2% or ±40ms whichever is greater
±0.2% or ±40ms whichever is greater
±0.5% or ±40ms whichever is greater
-
-
-
-
to 0
-
set
-
1MRK 502 074-BEN M