Injection equipment
Table 32. Electromagnetic compatibility tests
Test
1 MHz burst disturbance
100 kHz slow damped oscillatory wave immunity test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance test
Surge immunity test
Power frequency immunity test
Power frequency magnetic field test
Radiated electromagnetic field disturbance test
Radiated electromagnetic field disturbance test
Conducted electromagnetic field disturbance test
Voltage dips and short interruptions
Radiated emission
Conducted emission
Table 33. Insulation tests, REX060, REX062 and REG670
Test
Dielectric test
Impulse voltage test
Insulation resistance
Hitachi Power Grids
GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v4
© Copyright 2017 Hitachi Power Grids. All rights reserved
Type test values
2.5 kV
2.5 kV
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
1-2 kV, and 2-4 kV, 1.2/50 µs
High energy
150-300 V, 50 Hz
1000 A/m, 3 s
100 A/m, cont.
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m, 80-1000 MHz
10 V, 0.15-80 MHz
Dips:
40% /200 ms
70% /500 ms
Interruptions:
0-50 ms: No restart
0... ∞ s: Correct behaviour
at power down
30-1000 MHz
0.15-30 MHz
Type test values
2.0 kV AC, 1 min
5.0 kV, 1.2/50 µs, 0.5 J
>100 MΩ at 500V DC
1MRK 502 074-BEN M
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.3
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-8
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEC 60255-26
IEC 60255-26
Reference standard
IEC 60255-27
IEC 60255-27
IEC 60255-27