Table 22. BOM - Binary output module contact data (reference standard: IEC 61810-1)
Function or quantity
Binary outputs
Max system voltage
Min load voltage
Test voltage across open contact, 1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
Max operations with inductive load L/R ≤ 40 ms
Max operations with resistive load
Max operations with load
Max operations with no load
Making capacity for DC with L/R > 10 ms:
0.2 s
1.0 s
Making capacity at resistive load
0.2 s
1.0 s
Breaking capacity for AC, cos j > 0.4
Breaking capacity for DC with L/R < 40 ms
Operating time
Influencing factors
Table 23. Temperature and humidity influence
Parameter
Ambient temperature, operate
value
Relative humidity
Operative range
Storage temperature
Hitachi Power Grids
M12441-1 v11
M16705-1 v17
Reference value
+20±5°C
45-75%
0-95%
-
© Copyright 2017 Hitachi Power Grids. All rights reserved
Trip and Signal relays
24
250 V AC/DC
24V DC
1000 V rms
8 A
10 A
12 A
1000
2000
1000
10000
30 A
10 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
< 6 ms
Nominal range
-25°C to +55°C
10-90%
-40°C to +70°C
1MRK 502 074-BEN M
IP15846-1 v1
Influence
0.02%/°C
-
-