Generator protection REG670
Version 2.2
Control
Table 87. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Phase shift, j
- j
line
bus
Voltage high limit for synchronizing and synchrocheck
Reset ratio, synchrocheck
Frequency difference limit between bus and line for synchrocheck
Phase angle difference limit between bus and line for synchrocheck
Voltage difference limit between bus and line for synchronizing and
synchrocheck
Time delay output for synchrocheck when angle difference between
bus and line jumps from "PhaseDiff" + 2 degrees to "PhaseDiff" - 2
degrees
Frequency difference minimum limit for synchronizing
Frequency difference maximum limit for synchronizing
Maximum closing angle between bus and line for synchronizing
Breaker closing pulse duration
tMaxSynch, which resets synchronizing function if no close has been
made before set time
Minimum time to accept synchronizing conditions
Voltage high limit for energizing check
Reset ratio, voltage high limit
Voltage low limit for energizing check
Reset ratio, voltage low limit
Maximum voltage for energizing
Time delay for energizing check when voltage jumps from 0 to 90%
of Urated
Operate time for synchrocheck function when angle difference
between bus and line jumps from "PhaseDiff" + 2 degrees to
"PhaseDiff" - 2 degrees
Operate time for energizing function when voltage jumps from 0 to
90% of Urated
Hitachi Power Grids
M12359-1 v15
© Copyright 2017 Hitachi Power Grids. All rights reserved
Range or value
(-180 to 180) degrees
(50.0-120.0)% of UBase
> 95%
(0.003-1.000) Hz
(5.0-90.0) degrees
(0.02-0.5) p.u
(0.000-60.000) s
(0.003-0.250) Hz
(0.050-1.000) Hz
(15-30) degrees
(0.050-1.000) s
(0.000-6000.00) s
(0.000-60.000) s
(50.0-120.0)% of UBase
> 95%
(10.0-80.0)% of UBase
< 105%
(50.0-180.0)% of UBase
(0.000-60.000) s
Min. = 15 ms
Max. = 30 ms
Min. = 70 ms
Max. = 90 ms
1MRK 502 074-BEN M
Accuracy
-
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
-
±2.5 mHz
±2.0 degrees
±0.5% of U
r
±0.2% or ±35 ms whichever is
greater
±2.5 mHz
±2.5 mHz
±2.0 degrees
±0.2% or ±15 ms whichever is
greater
±0.2% or ±35 ms whichever is
greater
±0.2% or ±35 ms whichever is
greater
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
-
±0.5% of U
r
-
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
±0.2% or ±100 ms whichever is
greater
103