ABB Relion 670 Series Product Manual page 125

Generator protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Generator protection REG670
Version 2.2
Hardware
IED
Table 165. Case
Material
Front plate
Surface treatment
Finish
Table 166. Water and dust protection level according to IEC 60529
Front
Sides, top and bottom
Rear side
Table 167. Weight
Case size
6U, 1/2 x 19"
6U, 3/4 x 19"
6U, 1/1 x 19"
Electrical safety
Table 168. Electrical safety according to IEC 60255-27
Equipment class
Overvoltage category
Pollution degree
Connection system
Table 169. CT and VT circuit connectors
Connector type
Screw compression type
Terminal blocks suitable for ring lug terminals
Table 170. Auxiliary power supply and binary I/O connectors
Connector type
Screw compression type
Terminal blocks suitable for ring lug terminals
Hitachi Power Grids
Steel sheet
Stainless steel with cut-out for HMI
Aluzink preplated steel
Light grey (RAL 7035)
IP40 (IP54 with sealing strip)
IP40
IP20 with screw compression type
IP10 with ring lug terminals
Weight
£ 7.5 kg/16 lb
£ 15 kg/33 lb
£ 15 kg/33 lb
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v2
I (protective earthed)
III
2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
© Copyright 2017 Hitachi Power Grids. All rights reserved
M11778-1 v7
M12327-1 v5
M11777-1 v7
SEMOD53376-2 v6
Rated voltage and current
250 V AC, 20 A
250 V AC, 20 A
M12583-1 v8
Rated voltage
250 V AC
300 V AC
1MRK 502 074-BEN M
SEMOD53385-1 v1
GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
SEMOD53371-1 v1
Maximum conductor area
2
4 mm
(AWG12)
2
2 x 2.5 mm
(2 x AWG14)
2
4 mm
(AWG12)
Maximum conductor area
2
2.5 mm
(AWG14)
2
2 × 1 mm
(2 x AWG18)
2
3 mm
(AWG14)
125