Setting example
Ex.
To execute the interrupt program (I51) at the disconnection detection in any channel of the thermocouple input module
• Parameter setting
Set "Interrupt setting" of [Module Parameter] as follows.
No.
Condition target setting
2
Disconnection detection flag
• Label settings
Classification
Label name
Module Label
RCPU.stSM.bAlways_ON
RCPU.stSM.bAfter_RUN1_Scan_ON
R60TDG_1.unInterruptFactorMask_D[1].0
R60TDG_1.unInterruptFactorResetRequest_D[1].0
Labels to be defined
Define global labels as shown below:
(0)
Enable only the interrupt pointer I51.
(10)
Turn on 'Interrupt factor reset request [1]' (U0\G157).
Perform the processing of when disconnection is detected.
Condition target channel setting
All CH specification
Description
Always ON
ON for one scan after RUN
Interrupt factor mask
Interrupt factor reset request
Interrupt pointer
I51
Device
SM400
SM402
U0\G125.0
U0\G157.0
1 FUNCTIONS
1.11 Interrupt Function
1
61