Mitsubishi Electric MELSEC iQ-R Series User Manual page 38

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Any value
At the time of the disconnection detection, a value set in 'CH1 Conversion setting value at disconnection detection' (Un\G532)
is stored in 'CH1 Measured temperature value' (Un\G400). The default value of 'CH1 Conversion setting value at
disconnection detection' (Un\G532) is 0. The value can be changed to any value although using 0 is no problem.
When the scaling function is used, a value according to the setting of 'CH1 Conversion setting at
disconnection detection' (Un\G531) is scale converted and then stored as a scaling value.
Setting procedure
1.
Set "Disconnection detection function enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Application setting] 
[Disconnection detection function]
2.
Set "Disconnection detection Automatic clear enable/disable setting" to "Enable" or "Disable".
3.
Using "Conversion setting for disconnection detection", set what value is to be stored in 'CH1 Measured temperature
value' (Un\G400) at the time of the disconnection detection.
Item
Conversion setting at disconnection detection
4.
When "Given Value" is set, set "Conversion setting value for disconnection detection".
Item
Conversion setting value for disconnection detection
1 FUNCTIONS
36
1.7 Disconnection Detection Function
Setting range
• Upscale
• Downscale
• Given Value
• Value immediately before disconnection
Setting range
-3276.8 to 3276.7 ()