Mitsubishi Electric MELSEC iQ-R Series User Manual page 140

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Conversion enable/disable setting [Q compatible mode]
Set whether to enable or disable the temperature conversion with the Q compatible mode function used.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
(2)
(1) 0: Conversion enable, 1: Conversion disable
(2) The values of b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Conversion enable/disable setting (in Q
compatible mode)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Conversion disable (1) for all the channels.
CH1 Averaging process specification
Select processing to be performed among the sampling processing, averaging processing, and filter processing.
Averaging processing consists of time average, count average, and moving average.
Setting value
0
1
2
3
4
Setting a value other than the above causes an averaging process specification setting range error (error code: 191H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Averaging process specification
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Sampling processing (0) for all the channels.
APPX
138
Appendix 3 Buffer Memory Areas
b8
b7
b6
b5
b4
0
0
0
CH8
CH7
CH6
CH5
CH1
0
CH1
501
b3
b2
b1
b0
CH4
CH3
CH2
CH1
(1)
CH2
CH3
CH4
Setting content
Sampling processing
Time average
Count average
Moving average
Primary delay filter
CH2
CH3
CH4
701
901
1101
CH5
CH6
CH7
CH5
CH6
CH7
1301
1501
1701
CH8
CH8
1901

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60td8-gR60rd8-g

Table of Contents