Mitsubishi Electric MELSEC iQ-R Series User Manual page 125

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Condition target setting [n]
Set an interrupt factor to be detected.
Setting value
Setting content
0
Disable
1
Error flag (XF)
2
Alert output flag (Process alarm) (CH specification)
3
Alert output flag (Rate alarm) (CH specification)
4
Disconnection detection (CH specification)
5
Conversion completed flag (CH specification)
6
Logging hold flag (CH specification)
7
Logging read (CH specification)
Setting a value other than the above causes a condition target setting range error (error code: 181H).
When an input signal (X) or a buffer memory area set to 'Condition target setting [n]' (Un\G232 to Un\G247) turns off and on,
an interrupt request is sent to the CPU module. However, with the setting of Conversion completed flag (5), an interrupt
request is sent, provided that 'Conversion completed flag' (Un\G42) is on.
"n" indicates an interrupt setting number. (n = 1 to 16)
*1 For the thermocouple input module, power-on with the cold junction compensation resistor disconnected results in an interrupt being
detected since conversion of every channel is complete.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
1
Condition target setting [n]
232
Condition target setting [n] (in
4128
Q compatible mode)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (0) for all the channels.
*1
2
3
4
5
6
233
234
235
236
237
4129
4130
4131
4132
4133
7
8
9
10
11
238
239
240
241
242
4134
4135
4136
4137
4138
Appendix 3 Buffer Memory Areas
12
13
14
15
16
243
244
245
246
247
4139
4140
4141
4142
4143
APPX