Set the buffer memory area of a temperature input module to be refreshed.
This refresh setting eliminates the need for reading/writing data by programming.
1.
Start Module parameter.
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Refresh settings]
2.
Click "Target", and set the refresh destination.
• When "Target" is "Module Label"
Set whether to enable or disable the refresh by setting "Level data 0" to Enable or Disable.
• When "Target" is "Refresh Data Register (RD)"
The transfer destinations of all items are automatically set by setting the start device to "Top Device Name".
• When "Target" is "Device"
Double-click the item to be set to enter the refresh destination device.
3.
Click "Refresh Group" to set the timing to refresh.
Set "Refresh Group" to "At the Execution Time of END Instruction" or "At the Execution Time of Specified Program".
When "At the Execution Time of Specified Program" is set, double-click "Group [n] (n: 1-64)" and set a value of 1 to 64.
With refresh enabled, the value of the refresh destination takes effect at the timing of refresh which is set up
by the engineering tool. As this happens, the buffer memory is overwritten with the value of the refresh
destination. To change the value of a buffer memory area to be refreshed, change the value of module label or
device at the refresh destination in the program.