Toshiba BMS-TP0640ACE Manual page 88

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

Case 1
(In case that the indoor unit in which the fan is turned on and the unit with the adapter are same)
3
As the central control is available, push
When pushing the
(The operation on the remote controller is not accepted for approx. 1 minute after the
If the operation on the remote controller is not accepted for 1 minute or more after
incorrect address setup is considered.
In this case, automatic address is performed again. After approx. 5 minutes or more, and set up again the group
address from <procedure 1>.
Case 2
(In case that the indoor unit in which the fan is turned on and the unit from <procedure 1> with the
adapter are different)
As the central control is unavailable, change the address in the following procedure.
<Indoor unit without the adapter : Header indoor unit → → → → → Follower indoor unit.>
3
Using the setup temp
4
Check the setup data is
buttons.
5
Push the
button. In this time, the setup has finished if the display changes from flashing to
SET
lighting.
<Indoor unit with the adapter : Follower indoor unit → → → → → Header indoor unit.>
6
Push the
button to turn on the fan of the indoor unit attached with the adaptor.
UNIT
7
Using the setup temp
8
Check the setup data is
buttons.
9
Push the
button.
SET
<Reconfirmation of re-set up>
In this time, the setup has finished if the display changes from flashing to lighting.
10
When the above setup operation has finished, push the
of which setup has been changed. Using the setup temp
Item code 14 and check the changed contents.
Pushing the
button enables to clear the setup contents until now.
CL
(In this case, repeat the procedure from
11
Push
button. (Setup is determined.)
When pushing the
(The operation on the remote controller is not accepted for approx. 1 minute after the
pushed.)
If the operation on the remote controller is not accepted for 1 minute or more after
an incorrect address setup is considered.
In this case, automatic address is performed again. After approx. 5 minutes or more set up again the group
address from <procedure
button, the display disappears and the status returns to the normal stop status.
+
buttons, select Item code 14.
and change the setup data from
+
buttons, select Item code 14.
and change the setup data from
1
.)
button, the display disappears and the status returns to the normal stop status.
1
>.
button. (Setup is determined.)
UNIT
88
button has been pushed.)
button has been pushed, an
to
using the timer
to
using the timer
button to select the indoor unit
+
buttons, specify the
button has been
button has been pushed,
+
+