POINT 3
When the central control is performed for indoor units of twin control in a group control, it may be required
to change the group address. (Adapter is attached to the header indoor unit.)
Reason : The central control device communicates with individual indoor unit, header indoor unit of the
group control, and header indoor unit of twin control. However, as the address is automatically
set up, which unit will become the header unit is indefinite. Therefore if the unit attached with
adapter would not become the header indoor unit, a central control is unavailable.
Central
Central control wiring
control
devices
*Adapter
*TCB-PCNT30TLE
Central control is possible.
Line address
Indoor unit address
Group address
* A wired remote controller (RBC-AMT21E)
is required for address change.
How to check group address (Header/Follower indoor unit setup)
* Check the group address after confirming which unit is attached with the adapter.
<Procedure> Operation while air conditioner stops.
1
Push
+
+
SET
CL
2
The indoor unit in which the fan is turned on is the header indoor unit.
Indoor unit in which the fan is turned on = Indoor unit with the adapter : To Case 1
Indoor unit in which the fan is turned on = Indoor unit with the adapter : To Case 2
System A
Outdoor
Outdoor
Indoor
Indoor
(Header)
(Follower)
Remote
controller
1
2
1
1
1
2
buttons simultaneously for 4 seconds or more.
System B
Outdoor
Outdoor
Indoor
Indoor
*Adapter
(Follower
(Follower)
Header)
Remote
controller
Central control is impossible.
3
1
2
1
87
System C
Outdoor
Indoor
*Adapter
(Header
Follower)
Central control is possible.
4
5
1
1
2
1
2
Outdoor
Indoor
Remote
controller
6
1
0