Toshiba BMS-TP0640ACE Manual page 33

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

(17) Power meter input definition file
• File name: WHM_CH.DEF
• Power meter No. (1-64), interface address, channel No., pulse generator constants
• Used for energy monitoring and billing. No data is provided when energy monitoring and billing is not
performed.
• An interface address means the following:
1 to 31: energy monitoring interface
100 or more: pulse counter interface (Second digit: Intelligent Server No., first digit: Relay Interface
No.)
• Pulse generator constants (kWh/pulse): Used by the energy monitoring and billing Excel macro, but
not used by the controller.
(18) Report setup file
• File name: REPORT.DEF
• Daily report limit time (meter-read time), Monthly report limit date
(19) Operation mode setup file
• File name: RUN_MODE.DEF
• Operation mode range, scheduled operation central setting, door-lock interlocking central setting
• Operation mode range 0: all enabled, 16: cooling/dry/blowing, 32: heating/blowing
• Scheduled operation central setting
Setting
Stop (10 minutes later)
0
Stop
1
Stop + "run/stop" changeover
prohibition reset
2
Stop + "run/stop" changeover
prohibition reset
3
Stop + "run/stop" changeover
prohibition reset
• Door-lock interlocking central setting
Setting
0
Stop
1
Stop
2
Stop + "run/stop" changeover prohibited
3
Stop
* All these files must be included in "¥DEF" folder.
Stop (within 10 minutes)
Stop
Stop + "run/stop" changeover
prohibition reset
Stop + "run/stop" changeover
prohibited
Stop + "run/stop" changeover
prohibited
Lock (OFF to ON)
No operation
"Run/stop" changeover prohibition reset
"Run/stop" changeover prohibition reset
No operation
33
Run
Run
Run + "run/stop" changeover
prohibition reset
"Run/stop" changeover
prohibition reset
Run + "run/stop" changeover
prohibition reset
Unlock (ON to OFF)