4-3-1 (2) Manual setting from wired remote controller
Be sure to allocate Line (system) /Group/Indoor address one by one to match the address setting
table and setup file that is prepared beforehand.
If wrong value is set, a problem such as error of communication with air conditioner will occur.
Outdoor unit
Indoor unit
Remote
controller
Indoor address
Group address
Line address
At shipment, all address are 0099 (Address unset status)
(Step 1)
Arrange one indoor unit and one remote controller (RBC-AMT21E) set to 1 by 1.
Note:Don't use simple remote controller or wireless remote controller.
(Address setting is not available.)
CAUTION
Header
Follower
1
2
3
0
0
1
1
1
1
Line address
(At shipment:1)
Indoor, group, line
address are set
manually for each
refrigerant system
one by one.
4
2
1
Connect wired remote
controller individually
when manual address
setting
64
Dip Switch setting
on interface P.C.board