Toshiba BMS-TP0640ACE Manual page 75

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

• Automatic address setup procedure
Without central control : To the address setup procedure 1
With central control
(However, go to the procedure 1 when the central control is performed in a single
(Example)
Address setup
procedure
Cable systematic
diagram
Address setup procedure 1
1. Turn on power of indoor/outdoor units.
(In order of indoor → → → → → Outdoor)
2. After approx. 1 minute, check that U. 1. L08 (U. 1.
flash) is displayed in 7-segment display section on
the interface P.C. board of the header outdoor unit.
3. Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 refrigerant system (Usually,
approx. 5 minutes))
4. When the count Auto 1 → Auto 2 → Auto 3 is
displayed in 7-segment display section, and it
changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) ,
the setup finished.
5. When perform a central control, connect a relay
connector between [U1, U2] and [U3, U4] termi-
nals in the header unit.
REQUIREMENT
• When a group control is performed over the
multiple refrigerant systems, be sure to turn on
the power supplies of all the indoor units
connected in a group in the time of address
setup.
• If turning on the power for each refrigerant
system to set up address, a header indoor unit
is set for each line. Therefore, an alarm code
"L03" (Duplicated indoor header units) is output
in operation after address setup. In this case,
change the group address from the wired
remote controller so that only one header
indoor unit is set up.
: To the address setup procedure 2
In case of central control in a single
refrigerant system
To procedure 1
Outdoor
Outdoor
Central control
remote controller
Indoor
Indoor
Indoor
Remote
Remote
Remote
controller
controller
controller
In case of central control over
Outdoor
Central control
remote controller
Indoor
Indoor
Remote
controller
Header unit interface P.C. board
D600 D601 D602 D603 D604
5
(Example)
Wiring
systematic
diagram
75
refrigerant system
.)
refrigerant system
To procedure 2
Outdoor
Central control
remote controller
Indoor
Indoor
Indoor
Remote
Remote
controller
controller
3
SW04
SW05 SW15
2, 4
SW01
SW02 SW03
1
1
1
U1 U2
U3 U4
For internal
For wiring of
For internal
wiring between
central control
wiring between
indoor and
system
outdoor units
outdoor
Group control over multiple
refrigerant systems
Outdoor
Outdoor
Indoor
Indoor
Indoor
Remote
controller
U5 U6
Indoor